The Gold Standard for BLACKCOMB 061 Series Maintenance
Is your LUMINOR controller beeping or flashing a lamp replacement alert? Even if your current bulb is still glowing, its ability to kill pathogens significantly degrades after one year of use. The LUMINOR RL-470 is the only authorized replacement designed to work perfectly with the internal ballasts of your LB4-061, LB5-061, or LB6-061 system.
Why LUMINOR Lightlock™ & Construction Matters
The Lightlock™ system and LUMINOR’s build quality are performance safeguards for your home’s water.
-
Uniform Performance: Unlike generic bulbs, the RL-470 features a proprietary internal coating, providing a steady, uniform UV output throughout the entire 9,000-hour lifespan.
-
Industrial Strength: A proprietary ceramic lamp base ensures superior strength and product integrity compared to standard plastic alternatives.
-
Electronic Handshake: The included key tells your controller exactly which lamp is installed, ensuring the power supply delivers the precise wattage for optimal UV-C intensity.
-
Safety Compliance: Using non-genuine lamps can lead to “ballast stress” and will void your manufacturer’s warranty.
| Feature | Details |
| Model Number | RL-470 |
| Compatible Systems | LB4-061, LB5-061, LB6-061 |
| Replacement Sleeve | RQ-470 (Sold Separately) |
| Lamp Length | 18.5″ (470mm) |
| Wattage | 22 Watts |
| Base Color | Green |
| Expected Life | 1 Year (9,000 Hours) |
Notes
-
Replace the UV lamp every 12 months to maintain disinfection performance.
-
Dispose of used lamps in accordance with local regulations for mercury-containing products.
How to Replace Your RL-470 Lamp (Video Tutorial Below)
Replacing the lamp is a dry process. There is no need to drain the system.
Step 1. Obtain the correct lamp as shown on the silver label of the reactor or the maintenance parts screen.
Step 2. If a by-pass assembly is installed, shut the inlet valve off to prevent water flow through the system. Otherwise, turn off main water inlet valve (and/or turn off the water pump)
Step 3. Unplug the power for the controller. For 51/6.1 systems, remove and discard the Lamp Key from the controller
Step 4. Unscrew the captive ground screw from the ground lug on the UV reactor.
Step 5. Push down lamp cable and turn 1/4 turn counterclockwise to release lamp cable from gland nut.
Step 6. Disconnect and remove the old lamp from the chamber.
Step 7. The replacement lamp is packaged with a lamp key on the connector at the endo f the lamp. Remove the key from the lame and place it in the controller.
Step 8. Remove the lamp from its packaging, always holding the lamp by its ceramic ends (the use of cotton gloves is recommended).
Step 9. Insert the UV lamp into the reactor, being careful not to drop it.
Step 10. Plug the LUMI-loc lamp connector into the lamp, note the keying for proper alignment. Insert the lamp connector into the gland nut and turn the connector approximately 1/4 turn to lock.
Step 11. Tighten the captive ground screw to the ground lug on the UV reactor to ensure proper grounding.
Step 12. For 4.1 systems, reset the timer in the controller by holding down the button on the controller for 10 seconds.









Reviews
There are no reviews yet.